KESTREL
4100 HVAC WEATHER MONITORING |
Finally,
a hand held unit that measures everything you need to know on a
job site. The Kestrel 4100 is the new revolution in HVAC
monitoring.
·
Features
- Air flow in cfm, L/s, m³/s, m³/m, m³/h
- Air Velocity in ft/m, mph, m/s, km/h, kts, Beaufort
- Temperature in °F or °C
- Humidity in %
- Additional measurements of dewpoint, wind chill and heat
stress index
- Data Logger (automatic and manual)
- Minimum, Maximum and Average values
- Multi-Function 3-line display
- Impeller can be replaced without tools
- Humidity sensor can be recalibrated in the field with
our Relative Humidity Calibration Kit.
- Graphical Display for logged values
- Upload to a computer (with optional interface)
- Backlight for low light conditions
- Includes neck and wrist lanyards, protective pouch and
- 2 AAA batteries
- 2-year warranty
- Assembled in the USA
- US Patent Nos. 5,783,753 and 5,939,645 and 6,257,074
Specifications
Air
Velocity
- Accuracy ±3%
- Response Time 1 second
- Calibration Drift <2% after 100 hours use at
7m/s
- Units Display Resolution Range
- Knots KTS 0.1 0.6 to 78
- Meters per Second M/S 0.1 0.3 to 40
- Kilometers per Hour KM/H 0.1 1.0 to 144
- Miles per Hour MPH 0.1 0.7 to 89
- Feet per Minute FPM 1 59 to 7877
- Beaufort Force BEAU 1 1 to 16
Air
Flow
- Accuracy ±3%
- Response Time 1 second
- Calibration Drift <2% after 100 hours use at
7m/s
- Units Display Resolution Range
- Cubic Feet per Minute cfm 1 0 to 99,999
- Liters per Second L/s 1 0 to 99,999
- Cubic Meters per Second m³/s 1 0 to 99,999
- Cubic Meters per Minute m³/m 1 0 to 99,999
- Cubic Meters per Hour m³/h 1 0 to 99,999
Temperature
- Accuracy
- Temperature ±1°C
- Wind Chill ±1°C
- Dew Point ±2°C
- Heat Index ±3°C
- Response Time approximately 1 minute for most
conditions
- Units Display Resolution Range
- Celsius °C 0.1 -29 to 70
- Fahrenheit °F 0.1 -20 to 158
Relative
Humidity
- Accuracy ±3%
- Response Time approximately 1 minute for most
conditions
- Calibration Drift ±2% over 24 months (can be
field calibrated)
- Units Display Resolution Range Percent % 0.1 5 to
95%
Display
- Update 1 second
- Temperature Range Normal operation from -20°C to
60°C [-4°F to 140°F]. Below -20°C [-4°F], accurate
readings may be taken by keeping the unit warmer than -20°C
[-4°F] and exposing it for the minimum time necessary to
take a reading (less than 1 minute).
- Storage Temperature -30°C to 60°C [-22°F to
140°F]. Auto Shutdown After 15 minutes of no button
presses. (This feature can be disabled.)
Physical
- Battery Two AAA alkaline batteries (included).
Typical life, 400 hours.
- Impeller 25 mm. [1in.] diameter, sapphire
bearings, light weight. User-replaceable impeller/housing
assembly.
- Temperature Sensor Hermetically sealed precision
thermistor.
- Humidity Sensor Solid state silicon capacitive
sensor.
- Dimensions 12.7 x 4.5 x 2.8 cm. [5 x 1.8 x 1.1
in.]
- Weight 102 g. [3.6 oz.]
|